2 Parameters
2.2 List of parameters
SINAMICS G120D
268
List Manual (LH14), 01/2016, A5E33842313
Description:
Displays the reference quantity for power.
All power ratings specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency:
This value is calculated as follows:
Infeed: Calculated from voltage times current.
Closed-loop control: Calculated from torque times speed.
Refer to: p2000, p2001, p2002, p2003
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference power is calculated as follows:
- 2 * Pi * reference speed / 60 * reference torque (motor)
- reference voltage * reference current * root(3) (infeed)
Description:
Sets the reference quantity for angle.
All angles specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency:
This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting using
p0573 = 1.
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
Description:
Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Description:
Sets the reference quantity for acceleration rates.
All acceleration rates specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
r2004
Reference power / P_ref
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
14_10
Unit selection:
p0505
Func. diagram:
-
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
p2005
Reference angle / Reference angle
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
90.00 [°]
180.00 [°]
90.00 [°]
p2006
Reference temp / Ref temp
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
50.00 [°C]
300.00 [°C]
100.00 [°C]
p2007
Reference acceleration / a_ref
Access level:
4
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.01 [rev/s²]
500000.00 [rev/s²]
0.01 [rev/s²]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......