2 Parameters
2.2 List of parameters
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency:
Refer to: C01799
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Description:
Sets the time interval for carrying out the forced checking procedure and testing the safety motion monitoring
functions integrated in the drives.
Within the parameterized time, the safety functions must have been tested at least once (including de-selection of the
"STO" function).
This monitoring time is reset each time the test is carried out.
The signal source to initiate the forced checking procedure is set in p9705.
Dependency:
Refer to: p9705
Refer to: A01697, C01798
Note:
STO: Safe Torque Off
Description:
Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP A).
Dependency:
Refer to: p9556
Note:
The shutdown speed has no effect for a value = 0.
SS1: Safe Stop 1
Description:
Sets the SLS-specific stop response for the function "Safely Limited Speed" (SLS).
These settings apply to the individual limit values for SLS.
Value:
0:
STOP A
1:
STOP B
Index:
[0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLS4
Dependency:
Refer to: p9531
Note:
SLS: Safely Limited Speed
p9559
SI Motion forced checking procedure timer (processor 1) / SI Mtn dyn timer
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [h]
9000.00 [h]
8.00 [h]
p9560
SI Motion pulse suppression shutdown speed (processor 1) / SI Mtn IL v_sh P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
10.00 [rpm]
6000.00 [rpm]
10.00 [rpm]
p9563[0...3]
SI Motion SLS-specific stop response (processor 1) / SI Mtn SLS stop P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......