SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
531
2 Parameters
2.2 List of parameters
Description:
Sets the signal source of the switch setting I of instance BSW 1 of the binary changeover switch.
Description:
Display parameter for output quantity Q of instance BSW 1 of the binary changeover switch.
Description:
Setting parameter for the run-time group in which the instance BSW 1 of the binary changeover switch is to be called.
Value:
1:
Run-time group 1
2:
Run-time group 2
3:
Run-time group 3
4:
Run-time group 4
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance BSW 1 within the run-time group set in p20216.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source of input quantities X0 and X1 of instance NSW 0 of the numeric changeover switch.
Index:
[0] = Input X0
[1] = Input X1
p20214
BI: BSW 1 switch setting I / BSW 1 sw_setting
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7250
Min Max
Factory
setting
- - 0
r20215
BO: BSW 1 output Q / BSW 1 output Q
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7250
Min Max
Factory
setting
- - -
p20216
BSW 1 run-time group / BSW 1 RTG
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7250
Min Max
Factory
setting
1 9999
9999
p20217
BSW 1 run sequence / BSW 1 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7250
Min Max
Factory
setting
0 7999
590
p20218[0...1]
CI: NSW 0 inputs / NSW 0 inputs
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7250
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......