2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the control word of the setpoint channel.
Description:
Displays the status word for the ramp-function generator (RFG).
Note:
For bit 02:
The bit is the result of the OR logic operation - bit 00 and bit 01.
Description:
Sets the operating mode for flying restart.
The flying restart allows the drive converter to be switched on while the motor is still rotating. In so doing, the drive
converter output frequency is changed until the actual motor speed/velocity is found. The motor then accelerates up
to the setpoint at the ramp-function generator setting.
Value:
0:
Flying restart inactive
1:
Flying restart always active (start in setpoint direction)
4:
Flying restart always active (start only in setpoint direction)
r1198.0...15
CO/BO: Control word setpoint channel / STW setpoint chan
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2505
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed setp bit 0
Yes
No
3010
01
Fixed setp bit 1
Yes
No
3010
02
Fixed setp bit 2
Yes
No
3010
03
Fixed setp bit 3
Yes
No
3010
05
Inhibit negative direction
Yes
No
3040
06
Inhibit positive direction
Yes
No
3040
11
Setpoint inversion
Yes
No
3040
13
Motorized potentiometer raise
Yes
No
3020
14
Motorized potentiometer lower
Yes
No
3020
15
Bypass ramp-function generator
Yes
No
3060,
3070
r1199.0...8
CO/BO: Ramp-function generator status word / RFG ZSW
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3001, 3080
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ramp-up active
Yes
No
-
01
Ramp-down active
Yes
No
-
02
RFG active
Yes
No
-
03
Ramp-function generator set
Yes
No
-
04
Ramp-function generator held
Yes
No
-
05
Ramp-function generator tracking active
Yes
No
-
06
Maximum limit active
Yes
No
-
07
Ramp-function generator acceleration
positive
Yes
No
-
08
Ramp-function generator acceleration
negative
Yes
No
-
p1200[0...n]
Flying restart operating mode / FlyRest op_mode
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300
Min Max
Factory
setting
0 4 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......