SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
301
2 Parameters
2.2 List of parameters
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
Description:
Sets the delay time for comparing the speed with the maximum speed.
Dependency:
Refer to: p1082, r1084, r1087, p2162
Description:
Sets the time constant of the PT1 element to smooth the speed / velocity actual value.
The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and
signals.
Dependency:
Refer to: r2169
Description:
Sets the speed threshold value for the following messages:
p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8010, 8011, 8022
Min Max
Factory
setting
0.00 [rpm]
300.00 [rpm]
2.00 [rpm]
p2151[0...n]
CI: Speed setpoint for messages/signals / n_set for msg
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
8011
Min Max
Factory
setting
- - 1170[0]
p2152[0...n]
Delay for comparison n > n_max / Del n > n_max
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8023
Min Max
Factory
setting
0 [ms]
10000 [ms]
200 [ms]
p2153[0...n]
Speed actual value filter time constant / n_act_filt T
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8010
Min Max
Factory
setting
0 [ms]
1000000 [ms]
0 [ms]
p2155[0...n]
Speed threshold 2 / n_thresh val 2
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8010
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......