2 Parameters
2.2 List of parameters
Description:
Displays the actual motor-side position actual value for the motion monitoring functions on processor 1.
Note:
The display is updated in the safety monitoring clock cycle.
Description:
Displays the actual load-side actual values of both monitoring channels and their difference.
Index:
[0] = Load-side actual value on processor 1 (P1)
[1] = Load-side actual value on processor 2 (P2)
[2] = Load-side actual value difference P1 - P2
[3] = Load-side maximum actual value difference P1 - P2
[4] = Load-side actual value as safe position via PROFIsafe
[5] = Load-side additional actual value difference CU - second channel
Dependency:
Refer to: r9708, r9724
Note:
The value of this parameter is displayed in r9708 with units (mm or degrees).
The display is updated in the safety monitoring clock cycle.
For index 0:
The display of the load-side position actual value on processor 1 is updated in the monitoring clock cycle.
For index 1:
The display of the load-side position actual value on processor 2 is updated in the CDC clock cycle (r9724) and
delayed by one CDC clock cycle.
For index 2:
The difference between the load-side position actual value on processor 1 and load-side position actual value on
processor 2 is updated in the CDC clock cycle (r9724) and delayed by one CDC clock cycle.
For index 3:
The maximum difference between the load-side position actual value on processor 1 and the load-side position
actual value on processor 2.
For index 4:
The content corresponds to the value in index 0.
CDC: Crosswise Data Comparison
Description:
Displays the actual velocity values for the motion monitoring functions on processor 1.
Index:
[0] = Load-side velocity actual value on processor 1
[1] = Actual SAM/SBR velocity limit on processor 1
[2] = Actual SLS velocity limit on the processor 1
Dependency:
Refer to: r9732
Notice:
For index 2:
This SLS velocity limit can, as a result of conversion into the internal monitoring format, deviate from the specified
SLS velocity limit (see r9732).
Note:
The display is updated in the safety monitoring clock cycle.
r9712
CO: SI Motion diagnostics pos. act. val. motor side (processor 1) / SI Mtn s_act motP1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r9713[0...5]
CO: SI Motion diagnostics position actual value load side / SI Mtn s_act load
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r9714[0...2]
CO: SI Motion diagnostics velocity (processor 1) / SI Mtn diag v P1
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......