2 Parameters
2.2 List of parameters
SINAMICS G120D
124
List Manual (LH14), 01/2016, A5E33842313
Note:
AI: Analog Input
Description:
Displays the actual input voltage in V.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency:
The type of analog input AIx is set using p0756.
Refer to: p0756
Note:
AI: Analog Input
Description:
Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
AI: Analog Input
Description:
Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
AI: Analog Input
Description:
Sets the type of analog inputs.
p0756[0...1] = 0 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
Value:
0:
Unipolar voltage input (0 V ... +10 V)
8:
No sensor connected
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Analog input AI0 wire breakage
Yes
No
-
01
Analog input AI1 wire breakage
Yes
No
-
08
Analog input AI0 no wire breakage
Yes
No
-
09
Analog input AI1 no wire breakage
Yes
No
-
r0752[0...1]
CO: CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p0514
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
- - -
p0753[0...1]
CU analog inputs smoothing time constant / CU AI T_smooth
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
0.0 [ms]
1000.0 [ms]
0.0 [ms]
r0755[0...1]
CO: CO: CU analog inputs actual value in percent / CU AI value in %
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
- [%]
- [%]
- [%]
p0756[0...1]
CU analog inputs type / CU AI type
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
0 8 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......