SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
169
2 Parameters
2.2 List of parameters
Description:
Sets the maximum speed for the positive direction.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Display and connector output for the active positive speed limit.
Dependency:
Refer to: p1082, p1083, p1085
Description:
Sets the signal source for the speed limit of the positive direction.
Description:
Sets the speed limit for the negative direction.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Display and connector output for the active negative speed limit.
Dependency:
Refer to: p1082, p1086, p1088
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
p1083[0...n]
CO: Speed limit in positive direction of rotation / n_limit pos
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
210000.000 [rpm]
r1084
CO: Speed limit positive effective / n_limit pos eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050, 7958
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1085[0...n]
CI: Speed limit in positive direction of rotation / n_limit pos
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3050
Min Max
Factory
setting
- - 1083[0]
p1086[0...n]
CO: Speed limit in negative direction of rotation / n_limit neg
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
-210000.000 [rpm]
0.000 [rpm]
-210000.000 [rpm]
r1087
CO: Speed limit negative effective / n_limit neg eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050, 7958
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1088[0...n]
CI: Speed limit in negative direction of rotation / n_limit neg
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3050
Min Max
Factory
setting
- - 1086[0]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...