SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
41
2 Parameters
2.2 List of parameters
Description:
Displays the actual speed setpoint at the input of the speed controller or U/f characteristic (after the interpolator).
Dependency:
Refer to: r0020
Note:
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
Description:
Displays the unsmoothed actual speed values sensed by the encoders.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Reserved
Description:
Display and connector output for the speed setpoint after the setpoint filters.
Description:
Display and connector output for the speed actual value.
Frequency components from the slip compensation (for induction motors) are not included.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Calculated from f_set - f_slip (unsmoothed)
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization completed
Yes
No
-
01
De-magnetizing completed
Yes
No
-
02
Pulse enable available
Yes
No
-
03
Soft starting present
Yes
No
-
04
Magnetizing completed
Yes
No
-
05
Voltage boost when starting
Active
Inactive
6301
06
Acceleration voltage
Active
Inactive
6301
07
Frequency negative
Yes
No
-
08
Field weakening active
Yes
No
-
09
Voltage limit active
Yes
No
6714
10
Slip limit active
Yes
No
6310
11
Frequency limit active
Yes
No
-
12
Current limiting controller voltage output
active
Yes
No
-
13
Current/torque limiting
Active
Inactive
6060
r0060
CO: Speed setpoint before the setpoint filter / n_set before filt.
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
2701, 6030, 6799
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0061[0...2]
CO: Actual speed unsmoothed / n_act unsmoothed
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
4715
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0062
CO: Speed setpoint after the filter / n_set after filter
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6020, 6030, 6031
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0063[0...2]
CO: Speed actual value / n_act
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6020, 6799
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......