4 Faults and alarms
4.2 List of faults and alarms
F50518
FBLOCKS: Sampling time of free run-time group differs at download
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
In the STARTER/SCOUT project that was downloaded, the hardware sampling time of a free run-time group (1 <=
p20000[i] <= 256) was set to a value that was either too low or too high.
The sampling time must be between 1 ms and the value r20003 - r20002.
If the sampling time of the selected free run-time group is < 1 ms, the equivalent value of 1 ms is used.
If the value >= r20003, then the sampling time is set to the next higher or the same software sampling time >=
r21003.
Fault value (r0949, interpret decimal):
Number of the p20000 index of the run-time group where the sampling time is incorrectly set.
Number of the run-time group = fault value + 1
Remedy:
- correctly set the sampling time of the run-time group.
- if required, take all of the blocks from the run-time group.
Note:
Fault F50518 only detects an incorrectly parameterized run-time group. If, after correcting p20000[i] in the project,
this error occurs again at download, then the run-time group involved should be identified using the fault value
(r0949) and the sampling time correctly set.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......