2 Parameters
2.2 List of parameters
SINAMICS G120D
460
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the debounce time for the failsafe digital inputs used to control the "STO" function.
The debounce time is rounded to whole milliseconds.
Note:
The debounce time is rounded to whole milliseconds. It specifies the maximum duration of a fault pulse at the fail-
safe digital inputs with no reaction/influence on the selection or deselection of the Safety Basic Functions.
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
Description:
Sets the time interval for carrying out the forced checking procedure and testing the Safety switch-off signal paths.
Within the parameterized time, STO must have been de-selected at least once. The monitoring time is reset each
time that STO is de-selected.
Dependency:
Refer to: A01699
Note:
STO: Safe Torque Off
Description:
Displays the time remaining before dynamization and testing of the safety switch-off signal paths (forced checking
procedure).
Dependency:
Refer to: A01699
Description:
CRC via Node Identifier of the Control Unit.
Note:
CU: Control Unit
Description:
CRC via the Node Identifier of a Power Module.
p9651
SI STO debounce time (processor 1) / SI STO t_debou P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
1.00 [ms]
p9659
SI forced checking procedure timer / SI FCP Timer
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2810
Min Max
Factory
setting
0.00 [h]
9000.00 [h]
8.00 [h]
r9660
SI forced checking procedure remaining time / SI frc chk remain
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [h]
- [h]
- [h]
p9670
SI module identification Control Unit / Module ID CU
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 4294967295
0
p9672
SI module identifier Power Module / Module ID PM
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(95), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 4294967295
0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......