2 Parameters
2.2 List of parameters
SINAMICS G120D
82
List Manual (LH14), 01/2016, A5E33842313
Note:
The parameter applies for the following process data:
- Gx_XIST1
- Gx_XIST2 for reference mark or flying measurement
The fine resolution specifies the fraction between encoder pulses. Depending on the physical measurement principle,
an encoder pulse can be broken down into a different number of fractions (e.g. squarewave encoder: 2 bit =
resolution 4, sin/cos encoder: Typical 11 bit = resolution 2048).
For a squarewave encoder, with the factory setting, the least significant bits have the value zero, i.e. they do not
supply any useful information.
For especially high quality measuring systems, the fine resolution must be increased corresponding to the available
accuracy.
Description:
Sets the fine resolution in bits of the absolute position actual values.
Dependency:
Refer to: p0418
Note:
This parameter applies to process data Gx_XIST2 when reading the absolute value.
Description:
Sets the number of rotations that can be resolved for a rotary absolute encoder.
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Description:
Sets the resolution of the absolute position for a linear absolute encoder.
Notice:
This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note:
The serial protocol of an absolute encoder provides the position with a certain resolution, e.g. 100 nm. This value
must be entered here.
Description:
Sets the number of measuring steps per revolution for a rotary absolute encoder.
The resolution refers to the absolute position.
p0419[0...n]
Fine resolution absolute value Gx_XIST2 (in bits) / Enc fine Gx_XIST2
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
4704, 4710
Min Max
Factory
setting
2 18
2
p0421[0...n]
Absolute encoder rotary multiturn resolution / Enc abs multiturn
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
4704
Min Max
Factory
setting
0 4294967295
4096
p0422[0...n]
Absolute encoder linear measuring step resolution / Enc abs meas step
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS
Unit group:
-
Unit selection:
-
Func. diagram:
4704
Min Max
Factory
setting
0 [nm]
4294967295 [nm]
100 [nm]
p0423[0...n]
Absolute encoder rotary singleturn resolution / Enc abs singleturn
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
4704
Min Max
Factory
setting
0 1073741823
8192
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......