2 Parameters
2.2 List of parameters
SINAMICS G120D
114
List Manual (LH14), 01/2016, A5E33842313
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
Description:
Sets the thermal adaptation of the stator/primary section resistance and rotor/secondary section resistance according
to r0395 and r0396.
Value:
0:
No thermal adaptation of stator and rotor resistances
1:
Resistances adapted to the temperatures of the thermal model
2:
Resistances adapted to the measured stator winding temperature
Note:
For p0620 = 1, the following applies:
The stator resistance is adapted using the temperature in r0035 and the rotor resistance together with the model
temperature in r0633.
For p0620 = 2, the following applies:
The stator resistance is adapted using the temperature in r0035. If applicable, the rotor temperature for adapting the
rotor resistance is calculated from the stator temperature (r0035) as follows:
theta_R = (r0628 + r0625) / (r0627 + r0625) * r0035
Description:
Selects the identification of the stator resistance after booting the Control Unit (only for vector control).
The identification is used to measure the actual stator resistance and from the ratio of the result of motor data
identification (p0350) to the matching ambient temperature (p0625) the actual mean temperature of the stator
winding is calculated. The result is used to initialize the thermal motor model.
p0621 = 1:
Identification of the stator resistance only when the drive is switched on for the first time (pulse enable) after booting
the Control Unit.
p0621 = 2:
Identification of the stator resistance every time the drive is switched on (pulse enable).
Value:
0:
No Rs identification
1:
Rs identification after switching-on again
2:
Rs identification after switching-on each time
Dependency:
- perform motor data identification (see p1910) with cold motor.
- enter ambient temperature at time of motor data identification in p0625.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0622, r0623
Notice:
The calculated stator temperature can only be compared with the measured value of a temperature sensor
(KTY/PT1000) to a certain extent, as the sensor is usually the warmest point of the stator winding, whereas the
measured value of identification reflects the mean value of the stator winding.
Furthermore this is a short-time measurement with limited accuracy that is performed during the magnetizing phase
of the induction motor.
p0620[0...n]
Thermal adaptation, stator and rotor resistance / Mot therm_adapt R
Access level:
4
Calculated:
p0340 = 1
Data type:
Integer16
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 2 1
p0621[0...n]
Identification stator resistance after restart / Rst_ident Restart
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
MDS, p0130
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 2 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......