2 Parameters
2.2 List of parameters
SINAMICS G120D
218
List Manual (LH14), 01/2016, A5E33842313
Note:
(p0341 * p0342) + p1498 influence the speed/torque pre-control in encoderless operation.
Description:
Sets the scaling for the acceleration integrator at low speeds (only for encoderless torque control).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p0341, p0342
Description:
Sets the source for the torque setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
2:
Analog setpoint
6:
Fieldbus
7:
Analog setpoint 2
20:
Analog se no main setpoint
22:
Analog se analog setpoint
26:
Analog se fieldbus
27:
Analog se analog setpoint 2
60:
Fi no main setpoint
62:
Fi analog setpoint
66:
Ffieldbus
67:
Fi analog setpoint 2
70:
Analog setpoint 2 + no main setpoint
72:
Analog setpoint 2 + analog setpoint
76:
Analog setpoint 2 + fieldbus
77:
Analog setpoint 2 + analog setpoint 2
Dependency:
When changing this parameter, the following settings are influenced:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1503, p1511
Notice:
When executing a specific macro, the corresponding programmed settings are made and become active.
p1499[0...n]
Accelerating for torque control scaling / a for M_ctrl scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6030
Min Max
Factory
setting
0.0 [%]
400.0 [%]
100.0 [%]
p1500[0...n]
Torque setpoint selection / M_set sel
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 77
0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......