2 Parameters
2.2 List of parameters
SINAMICS G120D
330
List Manual (LH14), 01/2016, A5E33842313
Description:
Displays the smoothed speed setpoint of the technology controller prior to switching to operation with fault response
(see p2345).
Dependency:
Refer to: p2345
Note:
Smoothing time = 10 s
Description:
Sets the response of the technology controller to the occurrence of fault F07426 (technology controller actual value
limited).
The fault response is executed if status bit 8 or 9 in the technology controller status word r2349 is set. If both status
bits are zero, a switch back to technology controller operation will follow.
Value:
0:
Function inhibited
1:
On fault: Changeover to r2344 (or p2302)
2:
On fault: Changeover to p2215
Dependency:
The parameterized fault response is only effective if the technology controller mode is set to p2251 = 0 (technology
controller as main setpoint).
Refer to: p2267, p2268, r2344
Refer to: F07426
Notice:
Dependent upon the application, the changing over of the setpoint when fault F07426 occurs can lead to the fault
condition disappearing and the re-activation of the technology controller. This can repeat itself and cause limit
oscillations. In this case, a different fault response or a different fixed setpoint 15 for the fault response p2345 = 2
should be selected.
Note:
The parameterized fault response can only be achieved if the default fault response of the technology controller fault
F07426 is set to "NONE" (see p2100, p2101). If a fault response other than "NONE" is entered in p2101 for F07426,
p2345 must be set to zero.
If the fault occurs during ramping up to the starting setpoint p2302, this starting setpoint is retained as the final value
(there is no changeover to the fault response setpoint).
Description:
Display and BICO output for the status word of the technology controller.
r2344
CO: Technology controller last speed setpoint (smoothed) / Tec_ctrl n_setp_sm
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2345
Technology controller fault response / Tech_ctrl flt resp
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0 2 0
r2349.0...13
CO/BO: Technology controller status word / Tec_ctrl status
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Technology controller de-activated
Yes
No
-
01
Technology controller limited
Yes
No
-
02
Technology controller motorized
potentiometer limited max
Yes
No
-
03
Technology controller motorized
potentiometer limited min
Yes
No
-
04
Technology controller speed setpoint total in
setpoint channel
Yes
No
-
05
Technology controller RFG bypassed in the
setpoint channel
Yes
No
-
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......