2 Parameters
2.2 List of parameters
r0052.5 Quick stop active (OFF3)
r0052.6 Switching-on inhibited active
r0052.7 Alarm present
r0052.9 Control request
r0052.14 Motor rotates forwards
r0053.0 DC braking active
r0053.1 n_act > p2167 (n_off)
r0053.2 n_act <= p1080 (n_min)
r0053.3 I_act > p2170
r0053.4 n_act > p2155
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
Description:
Displays the status of digital outputs.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Inversion using p0748 has been taken into account.
Description:
Setting to invert the signals at the digital outputs.
Note:
DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Description:
Display and binector output for the status of the analog inputs.
r0747
CU digital outputs status / CU DO status
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2130, 2131, 2132,
2133
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (NO: X05.4)
High
Low
-
01
DO 1 (NO: X05.2)
High
Low
-
p0748
CU invert digital outputs / CU DO inv
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2241
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (NO: X05.4)
Inverted
Not inverted
-
01
DO 1 (NO: X05.2)
Inverted
Not inverted
-
r0751.0...9
BO: CU analog inputs status word / CU AI status word
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568
Min Max
Factory
setting
- - -
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......