SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
171
2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the skip bands.
Dependency:
Refer to: r1170
Note:
For bit 00:
With the bit set, the setpoint speed is within the skip band after the ramp-function generator (r1170).
The signal can be used to switch over the drive data set (DDS).
Description:
Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency:
Refer to: p1091, p1092, p1093, p1094
Note:
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
Description:
Sets the signal source for lowest possible motor speed.
Dependency:
Refer to: p1080
Notice:
The effective minimum speed is formed from p1080 and p1106.
Description:
Sets the signal source to select the total setpoint.
r1099.0
CO/BO: Skip band status word / Skip band ZSW
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
r1170 within the skip band
Yes
No
3050
p1101[0...n]
Skip speed bandwidth / n_skip bandwidth
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1106[0...n]
CI: Minimum speed signal source / n_min s_src
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3050
Min Max
Factory
setting
- - 0
p1108[0...n]
BI: Total setpoint selection / Total setp sel
Access level:
4
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3030
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......