SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
203
2 Parameters
2.2 List of parameters
Description:
Displays the amount by which the converter output voltage is reduced.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
Description:
Sets the proportional gain for the I_max voltage controller.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
Description:
Sets the integral time for the I_max voltage controller.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
For p1346 = 0, the following applies:
The integral time of the I_max voltage controller is de-activated.
Description:
Displays the economic factor determined for optimizing motor consumption.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1335
Note:
The value is only determined for operating modes with Economic (p1300 = 4, 7).
r1344
I_max controller voltage output / I_max_ctrl U_outp
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6300
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
p1345[0...n]
I_max voltage controller proportional gain / I_max_U_ctrl Kp
Access level:
3
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 7017
Min Max
Factory
setting
0.000 100000.000
0.000
p1346[0...n]
I_max voltage controller integral time / I_max_U_ctrl Tn
Access level:
3
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 7017
Min Max
Factory
setting
0.000 [s]
50.000 [s]
0.030 [s]
r1348
CO: U/f control Eco factor actual value / U/f Eco fac act v
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 6301
Min Max
Factory
setting
- [%]
- [%]
- [%]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......