2 Parameters
2.2 List of parameters
SINAMICS G120D
186
List Manual (LH14), 01/2016, A5E33842313
Note:
For bit 00 ... 09:
Used to control internal sequences during the flying restart.
Depending on the motor type (p0300), the number of active bits differs.
For bits 10 ... 15:
Are used to monitor the flying restart sequence.
Description:
Sets faults for which automatic restart should not be effective.
Dependency:
The setting is only effective for p1210 = 6, 16, 26.
Refer to: p1210
Description:
Sets the automatic restart mode (AR).
The parameters must be saved in the non-volatile memory p0971 = 1 in order that the setting becomes effective.
Value:
0:
Inhibit automatic restart
1:
Acknowledge all faults without restarting
4:
Restart after line supply failure w/o additional start attempts
6:
Restart after fault with additional start attempts
14:
Restart after line supply failure following man. acknowledgment
16:
Restart after fault following manual acknowledgment
26:
Acknowledging all faults and reclosing for an ON command
Recommendation:
For brief line supply failures, the motor shaft may still be rotating when restarting. The "flying restart" function (p1200)
might need to be activated to restart while the motor shaft is still rotating.
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Operator Panel in the LOCAL mode, then there is no automatic start.
For p1210 = 14, 16, a manual acknowledgment is required for an automatic restart.
Refer to: p0840, p0857
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is switched on
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is present again. This automatic switching-on operation can only be
interrupted by withdrawing the ON command.
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1). When faults
are present, therefore, the parameter cannot be changed.
For p1210 > 1, the motor is automatically started.
06
Speed adaptation circuit set I comp to 0
Yes
No
-
07
Current control on
Yes
No
-
08
Isd_set = 0 A
Yes
No
-
09
Frequency held
Yes
No
-
10
Search in the positive direction
Yes
No
-
11
Search Started
Yes
No
-
12
Current impressed
Yes
No
-
13
Search interrupted
Yes
No
-
14
Speed adaptation circuit deviation = 0
Yes
No
-
15
Speed control activated
Yes
No
-
p1206[0...9]
Automatic restart faults not active / AR fault not act
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p1210
Automatic restart mode / AR mode
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 26
0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......