2 Parameters
2.2 List of parameters
SINAMICS G120D
26
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
Ready
1:
Quick commissioning
2:
Power unit commissioning
3:
Motor commissioning
4:
Encoder commissioning
5:
Technological application/units
15:
Data sets
29:
Only Siemens int
30:
Parameter reset
39:
Only Siemens int
49:
Only Siemens int
95:
Safety Integrated commissioning
Note:
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
Ready
1:
Quick commissioning
2:
Power unit commissioning
3:
Motor commissioning
4:
Encoder commissioning
5:
Technological application/units
15:
Data sets
17:
Basic positioner commissioning
25:
Position control commissioning
29:
Only Siemens int
30:
Parameter reset
39:
Only Siemens int
49:
Only Siemens int
95:
Safety Integrated commissioning
Note:
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
p0010
Drive commissioning parameter filter / Drv comm. par_filt
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800, 2818
Min Max
Factory
setting
0 95
1
p0010
Drive commissioning parameter filter / Drv comm. par_filt
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800, 2818
Min Max
Factory
setting
0 95
1
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......