SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
461
2 Parameters
2.2 List of parameters
Note:
PM: Power Module
Description:
Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
Value:
0:
[00 hex] Copy function ended
29:
[1D hex] Start copy function node identifier
87:
[57 hex] Start copy function SI parameters
208:
[D0 hex] Start copy function SI basic parameters
Dependency:
Refer to: r3996
Notice:
When the parameters are copied, short-term communication interruptions may occur.
Note:
For value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
For value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9610 --> 9810, p9650 --> p9850, p9651 --> p9851
Description:
Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
Value:
0:
[00 hex] Data unchanged
172:
[AC hex] Acknowledge data change complete
220:
[DC hex] Acknowledge SI basic parameter change
236:
[EC hex] Acknowledge hardware CRC
Dependency:
Refer to: r9398, p9399, r9728, p9729, r9798, p9799, r9898, p9899
Note:
For value = AC and DC hex:
These values can only be set if the safety commissioning mode is set and the Safety Integrated password was
entered.
Description:
Sets the signal source for the test stop of the safety-relevant motion monitoring functions.
p9700
SI copy function / SI copy function
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95), U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0000 hex
00D0 hex
0000 hex
p9701
Acknowledge SI data change / Ackn SI data
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95), U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0000 hex
00EC hex
0000 hex
p9705
BI: SI Motion: Test stop signal source / SI Mtn test stop
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2837
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......