2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the corrective value for position actual value preprocessing.
Index:
[0] = Position control
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency:
Refer to: p2502, p2512, r2521, r2685
Note:
For BI: p2512[0] = 0/1 signal, the position actual value (CO: r2521[0]) is corrected corresponding to the value via CI:
p2513[0]. In so doing, the sign of the corrective value present is taken into account.
Description:
Sets the signal source to activate the function "set position actual value".
Index:
[0] = Position control
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency:
Refer to: p2502, p2515
Refer to: A07495, A07497
Warning:
As long as the position actual value is set, encoder increments that are received are not evaluated. In this state, any
position difference cannot be corrected!
Notice:
When the function "set position actual value" is activated while the function "reference mark search" or "measuring
probe evaluation" is activated, then the corresponding function is de-activated.
Note:
BI: p2514 = 1 signal:
The position actual value is set to the setting value in CI: p2515. Alarm A07497 "position setting value activated" is
output. Encoder increments that are received in the meantime, are not taken into account.
BI: p2514 = 1/0 signal:
The position actual value preprocessing is activated and is based on the setting value.
Description:
Sets the signal source for the setting value of the function "setting position actual value".
Index:
[0] = Position control
[1] = Encoder 1
[2] = Encoder 2
[3] = Reserved
Dependency:
Refer to: p2502, p2514
p2513[0...3]
CI: LR Position actual value preprocessing corrective value / Act val_prep corr
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
U32 / Integer32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4010, 4015
Min Max
Factory
setting
- - [0]
2685[0]
[1] 0
[2] 0
[3] 0
p2514[0...3]
BI: LR activate position actual value setting / s_act setting act
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4010
Min Max
Factory
setting
- - 0
p2515[0...3]
CI: LR position actual setting setting value / s_act set setVal
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
U32 / Integer32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4010
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......