2 Parameters
2.2 List of parameters
SINAMICS G120D
112
List Manual (LH14), 01/2016, A5E33842313
Description:
Setting to activate the motor temperature model.
Dependency:
For synchronous motors and synchronous reluctance motors, when exiting commissioning, temperature model 1 is
automatically activated if a time constant has been entered in p0611.
Refer to: r0034, p0604, p0605, p0606, p0611, p0613, p0615, p0625, p0626, p0627, p0628, r0630, r0631, r0632,
r0633, p5350, r5389, p5390, p5391
Refer to: F07011, A07012, A07014, A07910
Notice:
For bit 00:
This bit is only automatically activated for permanent-magnet 1FT7 synchronous motors and synchronous reluctance
motors. For other permanent-magnet synchronous motors, the user himself must activate motor temperature model
1 (I2t).
It is only possible to activate this motor temperature model (I2t) for a time constant greater than zero (p0611 > 0).
Note:
Mot_temp_mod: motor temperature model
For bit 00:
This bit is used to activate/de-activate the motor temperature model for permanent-magnet synchronous motors and
synchronous reluctance motors.
For bit 01 (see also bit 9):
This bit is used to activate/de-activate the motor temperature model for induction motors.
For bit 02:
This bit is used to activate/de-activate the motor temperature model for 1FK7 Basic and 1FL5 motors.
Motor temperature model 3 cannot be simultaneously activated with another motor temperature model.
For bit 08:
This bit is used to extend the motor temperature model 1 (I2t).
The following applies for firmware version < 4.7 SP6 (only bit 0):
- this bit has no function. Temperature model 1 operates in the standard mode.
Overtemperature at rated load: p0605 - 40 °C
Alarm threshold: p0605
Fault threshold: p0615
The following applies from firmware version 4.7 SP6 (bits 0 and 8):
- temperature model 1 operates in the extended mode.
Overtemperature at rated load: p0627
Alarm threshold: p5390
Fault threshold: p5391
For bit 09:
This bit is used to extend the motor temperature model 2.
For firmware version < 4.7 following applies (only bit 1):
- this bit has no function. Temperature model 2 operates in the standard mode.
From firmware version 4.7 the following applies (bits 1 and 9):
- this bit should be set. Temperature model 2 then operates in the extended mode and the result of the model is more
precise.
p0612[0...n]
Mot_temp_mod activation / Mot_temp_mod act
Access level:
2
Calculated:
p0340 = 1
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
8017, 8018
Min Max
Factory
setting
-
-
0000 0010 0000 0010 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Activate mot_temp_mod 1 (I2t)
Yes
No
-
01
Activate mot_temp_mod 2
Yes
No
-
02
Activate mot_temp_mod 3
Yes
No
-
08
Activate mot_temp_mod 1 (I2t) extensions
Yes
No
-
09
Activate mot_temp_mod 2 extensions
Yes
No
-
12
Mot_temp_mod 1 (I2t) ambient temperature
can be adjusted
Yes (via p0613)
No (fixed 20 °C)
-
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......