2 Parameters
2.2 List of parameters
SINAMICS G120D
432
List Manual (LH14), 01/2016, A5E33842313
The combination of device ID (r8909) and DAP ID uniquely identifies a PROFINET access point.
Note:
List of the SINAMICS DAP IDs:
20007 hex: CBE20 V4.5
20008 hex: CBE20 V4.6
20107 hex: CU310-2 PN V4.5
20108 hex: CU310-2 PN V4.6
20307 hex: CU320-2 PN V4.5
20308 hex: CU320-2 PN V4.6
20407 hex: CU230P-2 PN /CU240x-2 PN V4.5
20408 hex: CU230P-2 PN /CU240x-2 PN /CU250S-2 PN /G110M PN V4.6
20507 hex: CU250D-2 PN V4.5
20508 hex: CU250D-2 PN V4.6
Description:
Displays the controller assignment of a PROFINET subslot on the actual drive object.
Index:
[0] = Subslot 2 PROFIsafe
[1] = Subslot 3 PZD telegram
[2] = Subslot 4 PZD supplementary data
Dependency:
Refer to: r8961, r8962
Note:
Example:
If the parameter contains the value 2 in index [1], then this means that subslot 3 is assigned to controller 2.
Description:
Displays the IP address of the first PROFINET controller connected with the device via PN onboard.
Description:
Displays the IP address of the second PROFINET controller connected with the device via PN onboard.
Description:
Sets the profile for Ethernet/IP.
Value:
0:
SINAMICS
1:
ODVA AC/DC
r8960[0...2]
PN subslot controller assignment / PN subslot assign
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 8 -
r8961[0...3]
PN IP Address Remote Controller 1 / IP Addr Rem Ctrl1
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 255
-
r8962[0...3]
PN IP Address Remote Controller 2 / IP Addr Rem Ctrl2
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 255
-
p8980
Ethernet/IP profile / Eth/IP profile
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2473
Min Max
Factory
setting
0 1 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......