SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
865
4 Faults and alarms
4.2 List of faults and alarms
In these cases, when the minimum limit is violated then the parameter value is rounded up and when the maximum
limited is violated the parameter value is rounded down.
Fault value (r0949, interpret decimal):
Diagnostics parameter r9451 to display all parameters whose value had to be adapted.
See also: p0100 (IEC/NEMA mot stds), p0505 (Selecting the system of units), p0595 (Technological unit selection)
Remedy:
Check the adapted parameter values and if required correct.
See also: r9451 (Units changeover adapted parameters)
A07089
Changing over units: Function module activation is blocked because the units have
been changed over
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An attempt was made to activate a function module. This is not permissible if the units have already been changed
over.
See also: p0100 (IEC/NEMA mot stds), p0505 (Selecting the system of units)
Remedy:
Restore units that have been changed over to the factory setting.
A07092
Drive: moment of inertia estimator still not ready
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The moment of inertia estimator still has no valid values.
The acceleration cannot be calculated.
The moment of inertia estimator is ready, if the frictional values (p1563, p1564) as well as the moment of inertia value
(p1493) have been determined (r1407.26 = 1).
Remedy:
Repeat the operation when the moment of inertia estimator is ready (r1407.26 = 1).
A07094
General parameter limit violation
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
NONE
Cause:
As a result of the violation of a parameter limit, the parameter value was automatically corrected.
Minimum limit violated --> parameter is set to the minimum value.
Maximum limit violated --> parameter is set to the maximum value.
Alarm value (r2124, interpret decimal):
Parameter number, whose value had to be adapted.
Remedy:
Check the adapted parameter values and if required correct.
A07200
Drive: Master control ON command present
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The ON/OFF1 command is present (no 0 signal).
The command is either influenced via binector input p0840 (current CDS) or control word bit 0 via the master control.
Remedy:
Switch the signal via binector input p0840 (current CDS) or control word bit 0 via the master control to 0.
F07220 (N, A)
Drive: Master control by PLC missing
Message class:
Communication error to the higher-level control system (9)
Reaction:
OFF1 (NONE, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The "master control by PLC" signal was missing in operation.
- interconnection of the binector input for "master control by PLC" is incorrect (p0854).
- the higher-level control has withdrawn the "master control by PLC" signal.
- data transfer via the fieldbus (master/drive) was interrupted.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......