SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
223
2 Parameters
2.2 List of parameters
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description:
Sets the scaling for the lower torque limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description:
Display and connector output for the upper torque limit of all torque limits without offset.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
Description:
Display and connector output for the lower torque limit of all torque limits without offset.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
Description:
Sets the signal source for the scaling of the upper torque limit in p1522.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1525[0...n]
CO: Torque limit lower scaling / M_max lower scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
r1526
CO: Torque limit upper without offset / M_max up w/o offs
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6060, 6630, 6640
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r1527
CO: Torque limit lower without offset / M_max low w/o offs
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6060, 6630, 6640
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
p1528[0...n]
CI: Torque limit upper scaling / M_max upper scal
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
- - 1524[0]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......