4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
852
List Manual (LH14), 01/2016, A5E33842313
A01900 (F)
PROFIBUS: Configuration telegram error
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A PROFIBUS master attempts to establish a connection using an incorrect configuring telegram.
Alarm value (r2124, interpret decimal):
2: Too many PZD data words for input or output. The number of possible PZD is specified by the number of indices in
r2050/p2051.
3: Uneven number of bytes for input or output.
211: Unknown parameterizing block.
501: PROFIsafe parameter error (e.g. F_dest).
502: PROFIsafe telegram does not match.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
Check the bus configuration on the master and slave sides.
For alarm value = 2:
Check the number of data words for input and output.
For alarm value = 211:
Ensure offline version <= online version.
For alarm value = 501:
Check the set PROFIsafe address (p9610).
For alarm value = 502:
Check the enable of F-DI (p9501.30).
F01910 (N, A)
Fieldbus interface setpoint timeout
Message class:
Communication error to the higher-level control system (9)
Reaction:
OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The reception of setpoints from the fieldbus interface has been interrupted.
- bus connection interrupted.
- communication partner switched off.
For PROFIBUS:
- PROFIBUS master set into the STOP state.
See also: p2047 (PROFIBUS additional monitoring time)
Remedy:
Ensure bus connection has been established and switch on communication partner.
- if required, adapt p2040.
For PROFIBUS:
- set the PROFIBUS master to the RUN state.
- if the error is repeated, check the set response monitoring in the bus configuration (HW Config).
- slave redundancy: For operation on a Y link, it must be ensured that "DP alarm mode = DPV1" is set in the slave
parameterization.
A01920 (F)
PROFIBUS: Interruption cyclic connection
Message class:
Communication error to the higher-level control system (9)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic connection to the PROFIBUS master is interrupted.
Remedy:
Establish the PROFIBUS connection and activate the PROFIBUS master in the cyclic mode.
Note:
If there is no communication to a higher-level control system, then p2030 should be set = 0 to suppress this
message.
See also: p2030 (Field bus int protocol selection)
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......