SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
303
2 Parameters
2.2 List of parameters
Description:
Sets the speed threshold value for the signal "|n_act| < speed threshold value 3" (BO: r2199.0).
Dependency:
Refer to: p2150, r2199
Description:
Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max" (BO: r2197.6).
Dependency:
Refer to: r1084, r1087, r2197
Notice:
For p0322 = 0, the following applies: p2162 <= 0.1 * p0311
For p0322 > 0, the following applies: p2162 <= 1.02 * p0322 - p1082
If one of the conditions is violated, p2162 is appropriately and automatically reduced when exiting the commissioning
mode.
Note:
For a negative speed limit (r1087) the hysteresis is effective below the limit value and for a positive speed limit
(r1084) above the limit value.
If significant overshoot occurs in the maximum speed range (e.g. due to load shedding), you are advised to increase
the dynamic response of the speed controller (if possible). If this is insufficient, the hysteresis p2162 can only be
increased by more than 10% of the rated speed when the maximum speed (p0322) of the motor is sufficiently greater
than the speed limit p1082.
Description:
Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2164, p2166, r2197
Description:
Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off"
signal/message (BO: r2197.7).
Dependency:
Refer to: p2163, p2166, r2197
p2161[0...n]
Speed threshold 3 / n_thresh val 3
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8010, 8011
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
5.00 [rpm]
p2162[0...n]
Hysteresis speed n_act > n_max / Hyst n_act>n_max
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8010
Min Max
Factory
setting
0.00 [rpm]
60000.00 [rpm]
0.00 [rpm]
p2163[0...n]
Speed threshold 4 / n_thresh val 4
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8011
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
90.00 [rpm]
p2164[0...n]
Hysteresis speed 4 / n_hysteresis 4
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8011
Min Max
Factory
setting
0.00 [rpm]
200.00 [rpm]
2.00 [rpm]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......