4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
820
List Manual (LH14), 01/2016, A5E33842313
23: Format illegal.
24: Number of values not consistent.
108: Unit unknown.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
- enter the correct value in the specified parameter.
- identify the parameter that restricts the limits of the specified parameter.
F01043
Fatal error at project download
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A fatal error was detected when downloading a project using the commissioning software.
Fault value (r0949, interpret decimal):
1: Device status cannot be changed to Device Download (drive object ON?).
2: Incorrect drive object number.
8: Maximum number of drive objects that can be generated exceeded.
11: Error while generating a drive object (global component).
12: Error while generating a drive object (drive component).
13: Unknown drive object type.
14: Drive status cannot be changed to "ready for operation" (r0947 and r0949).
15: Drive status cannot be changed to drive download.
16: Device status cannot be changed to "ready for operation".
18: A new download is only possible if the factory settings are restored for the drive unit.
20: The configuration is inconsistent.
21: Error when accepting the download parameters.
22: SW-internal download error.
100: The download was canceled, because no write requests were received from the commissioning client (e.g. for
communication error).
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
- use the current version of the commissioning software.
- modify the offline project and download again (e.g. compare the motor and Power Module in the offline project and
on the drive).
- change the drive state (is a drive rotating or is there a message/signal?).
- carefully note any other messages/signals and remove their cause.
- boot from previously saved files (switch-off/switch-on or p0970).
F01044
CU: Descriptive data error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error was detected when loading the descriptive data saved in the non-volatile memory.
Remedy:
Replace the memory card or Control Unit.
A01045
Configuring data invalid
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected when evaluating the parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX, or
CCxxxyyy.ACX saved in the non-volatile memory. Because of this, under certain circumstances, several of the saved
parameter values were not able to be accepted. Also see r9406 up to r9408.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......