SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
165
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for jog 2.
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
Description:
Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
Refer to: p1055, p1056
Description:
Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
Refer to: p1055, p1056
Description:
Sets the speed limit effective in the setpoint channel.
Dependency:
Refer to: p1082, p1083, p1085, p1086, p1088
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501, 3030
Min Max
Factory
setting
- - 0
p1058[0...n]
Jog 1 speed setpoint / Jog 1 n_set
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3001, 3030
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
150.000 [rpm]
p1059[0...n]
Jog 2 speed setpoint / Jog 2 n_set
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3001, 3030
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
-150.000 [rpm]
p1063[0...n]
Setpoint channel speed limit / Setp_chan n_lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3040
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
210000.000 [rpm]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......