2 Parameters
2.2 List of parameters
SINAMICS G120D
556
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the signal source for the input pulse I of instance MFP 3 of the pulse generator.
Description:
Setting parameter for pulse duration T in milliseconds of instance MFP 3 of the pulse generator.
Description:
Display parameter for output pulse Q of instance MFP 3 of the pulse generator.
Description:
Setting parameter for the run-time group in which the instance MFP 3 of the pulse generator is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance MFP 3 within the run-time group set in p20362.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source for input X of the polyline (20 breakpoints) of instance PLI 0.
p20359
BI: MFP 3 input pulse I / MFP 3 inp_pulse I
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7230
Min Max
Factory
setting
- - 0
p20360
MFP 3 pulse duration in ms / MFP 3 pulse_dur ms
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7230
Min Max
Factory
setting
0.00 5400000.00
0.00
r20361
BO: MFP 3 output Q / MFP 3 output Q
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7230
Min Max
Factory
setting
- - -
p20362
MFP 3 run-time group / MFP 3 RTG
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7230
Min Max
Factory
setting
5 9999
9999
p20363
MFP 3 run sequence / MFP 3 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7230
Min Max
Factory
setting
0 32000
960
p20372
CI: PLI 0 input X / PLI 0 input X
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7226
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......