2 Parameters
2.2 List of parameters
SINAMICS G120D
48
List Manual (LH14), 01/2016, A5E33842313
Value:
0:
IEC-Motor (50 Hz, SI units)
1:
NEMA motor (60 Hz, US units)
2:
NEMA motor (60 Hz, SI units)
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0337, p1800
Note:
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
Description:
Identification of the Control Unit using an LED.
Note:
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
Description:
Configuration of the motor when commissioning the motor.
Dependency:
For standard induction motors (p0301 > 10000), bit 0 is automatically pre-assigned the connection type of the
selected data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
Refer to: p0304, p0305, p1082
Note:
For bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically
converted to the selected connection type (star/delta).
For bit 01:
87 Hz operation is only possible in the delta connection type. When selected, the maximum speed p1082 is
automatically pre-assigned for a maximum output frequency of 87 Hz.
Description:
Sets the number of Command Data Sets (CDS).
Dependency:
Refer to: p0010, r3996
Notice:
When the data sets are created, short-term communication interruptions may occur.
Note:
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0124[0...n]
CU detection via LED / CU detection LED
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
U, T
Scaling:
-
Dyn. index:
PDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0
p0133[0...n]
Motor configuration / Motor config
Access level:
2
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor connection type
Delta
Star
-
01
Motor 87 Hz operation
Yes
No
-
p0170
Number of Command Data Sets (CDS) / CDS count
Access level:
2
Calculated:
-
Data type:
Unsigned8
Can be changed:
C(15)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8560
Min Max
Factory
setting
2 4 2
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......