SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
127
2 Parameters
2.2 List of parameters
Dependency:
The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note:
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
Description:
Sets the simulation mode for digital inputs.
Dependency:
The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note:
This parameter is not saved when data is backed up (p0971).
DI: Digital Input
Description:
Sets the setpoint for the input signals in the digital input simulation mode.
Dependency:
The simulation of a digital input is selected using p0795.
Refer to: p0795
Note:
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI0 (X07.1)
Simulation
Terminal eval
-
01
DI1 (X07.2)
Simulation
Terminal eval
-
02
DI2 (X08.1)
Simulation
Terminal eval
-
03
DI3 (X08.2)
Simulation
Terminal eval
-
04
DI4 (X09.1)
Simulation
Terminal eval
-
05
DI5 (X09.2)
Simulation
Terminal eval
-
11
DI11 (X10.3, 7) AI0
Simulation
Terminal eval
-
12
DI12 (X10.4, 7) AI1
Simulation
Terminal eval
-
p0795
CU digital inputs simulation mode / CU DI simulation
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2201, 2210, 2256
Min Max
Factory
setting
-
-
0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI0 (X07.1)
Simulation
Terminal eval
-
01
DI1 (X07.2)
Simulation
Terminal eval
-
02
DI2 (X08.1)
Simulation
Terminal eval
-
03
DI3 (X08.2)
Simulation
Terminal eval
-
04
DI4 (X09.1)
Simulation
Terminal eval
-
05
DI5 (X09.2)
Simulation
Terminal eval
-
p0796
CU digital inputs simulation mode setpoint / CU DI simul setp
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2201, 2210, 2256
Min Max
Factory
setting
-
-
0000 0000 0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X07.4)
High
Low
-
01
DI 1 (X07.2)
High
Low
-
02
DI 2 (X08.4)
High
Low
-
03
DI 3 (X08.2)
High
Low
-
04
DI 4 (X09.4)
High
Low
-
05
DI 5 (X09.2)
High
Low
-
11
DI 11 (X10.3) AI 0
High
Low
-
12
DI 12 (X10.4) AI 1
High
Low
-
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......