2 Parameters
2.2 List of parameters
SINAMICS G120D
408
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the positive tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, then the pulse number is not corrected. If it is higher than this limit, fault F3x131
is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency:
Refer to: p0437, p4688
Refer to: F31131
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
The positive limit describes additional pulses due to EMC.
Description:
Sets the negative tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, the PPR is not corrected. If it is higher than this limit, fault F3x131 is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency:
Refer to: p0437, p4681, p4688
Refer to: F31131
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -1001, the negated value of p4681 is effective.
The negative limit describes the pulses lost due to a covered glass panel in the incremental encoder.
Description:
Sets the positive tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
Accumulator (p4688) is compared with this parameter, and where relevant, alarm A3x422 is output for 5 seconds.
Dependency:
Refer to: p0437, p4681, p4682, p4688
Refer to: F31131, A31422
Note:
Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
Description:
Sets the negative tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
Accumulator (p4688) is compared with this parameter, and where relevant, alarm A3x422 is output for 5 seconds.
p4681[0...n]
Zero mark monitoring tolerance window limit 1 positive / ZM tol lim 1 pos
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1000
2
p4682[0...n]
Zero mark monitoring tolerance window limit 1 negative / ZM tol lim 1 neg
Access level:
3
Calculated:
-
Data type:
Integer32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-1001 0
-1001
p4683[0...n]
Zero mark monitoring tolerance window alarm threshold positive / ZM tol A_thr pos
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 100000
0
p4684[0...n]
Zero mark monitoring tolerance window alarm threshold negative / ZM tol A_thr neg
Access level:
3
Calculated:
-
Data type:
Integer32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-100001 0
-100001
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......