209
2 Parameters
2.2 List of parameters
Description:
Sets the smoothing time for the actual speed value of the speed controller for closed-loop control with encoder.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
Description:
Displays the sum of all speed setpoints that are present.
The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- speed setpoint 1 (p1155).
- speed setpoint 2 (p1160).
- speed setpoint for the speed pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r1119, p1155, p1160
Description:
Display and connector output for the actual smoothed speed actual value of the speed control.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Sets the smoothing time for the actual speed of the speed controller for encoderless closed-loop speed control.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
p1442[0...n]
Speed controller speed actual value smoothing time / n_ctr n_act T_smth
Access level:
2
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6020, 6040
Min Max
Factory
setting
0.00 [ms]
32000.00 [ms]
4.00 [ms]
r1444
Speed controller speed setpoint steady-state (static) / n_ctrl n_set stat
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
5030
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r1445
CO: Actual speed smoothed / n_act smooth
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6040
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1452[0...n]
Speed controller speed actual value smoothing time (sensorless) / n_C n_act T_s SL
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6020, 6040
Min Max
Factory
setting
0.00 [ms]
32000.00 [ms]
10.00 [ms]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......