2 Parameters
2.2 List of parameters
SINAMICS G120D
142
List Manual (LH14), 01/2016, A5E33842313
Description:
Display and BICO output for the status word and control word of the drive coupling.
Note:
For bit 01:
Bit 1 is used to control an external line contactor.
Description:
Sets the main contactor holding time after OFF1
Dependency:
Refer to: p0869
Note:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switching-on inhibited must be
acknowledged via the source of p0840 = 0 (OFF1) – and before the main contactor holding time expires, should go
back to 1, otherwise the main contactor will open.
When operating a drive connected to SINUMERIK, which only closes the main contactor with the OFF1 command
(blocksize, chassis), p0867 should be set as a minimum to 50 ms.
Description:
Sets the configuration for the sequence control.
Dependency:
Refer to: p0867
Note:
For bit 00:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switching-on inhibited must be acknowledged via the source of p0840 =
0 (OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the main
contactor will open.
Description:
Sets the signal source to select the "parking axis" function.
r0863.0...1
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Closed-loop control operation
Yes
No
-
01
Energize contactor
Yes
No
2634
p0867
Power unit main contactor holding time after OFF1 / PU t_MC after OFF1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.0 [ms]
500.0 [ms]
50.0 [ms]
p0869
Sequence control configuration / Seq_ctrl config
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Keep main contactor closed for STO
Yes
No
-
p0897
BI: Parking axis selection / Parking axis sel
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......