2 Parameters
2.2 List of parameters
SINAMICS G120D
44
List Manual (LH14), 01/2016, A5E33842313
Description:
Displays the maximum output voltage.
Dependency:
The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note:
As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link
voltage.
Description:
Display and connector output for the actual output voltage of the power unit.
Dependency:
Refer to: r0025
Note:
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
Description:
Displays the maximum modulation depth.
Dependency:
Refer to: p1803
Description:
Display and connector output for the actual modulation depth.
Dependency:
Refer to: r0028
Note:
For space vector modulation, 100% corresponds to the maximum output voltage without overcontrol.
Values above 100 % indicate an overcontrol condition - values below 100% have no overcontrol.
The phase voltage (phase-to-phase, rms) is calculated as follows:(r0074 x r0070) / (sqrt(2) x 100 %).
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
r0071
Maximum output voltage / U_output max
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6301, 6640, 6700,
6722, 6723, 6724, 6725, 6727
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r0072
CO: Output voltage / U_output
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
5700, 6730, 6731,
6799
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r0073
Maximum modulation depth / Modulat_depth max
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6723, 6724
Min Max
Factory
setting
- [%]
- [%]
- [%]
r0074
CO: Modulat_depth / Mod_depth
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
5730, 6730, 6731,
6799, 8940, 8950
Min Max
Factory
setting
- [%]
- [%]
- [%]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......