SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
235
2 Parameters
2.2 List of parameters
Description:
Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
The parameter is effective for permanent-magnet synchronous motors.
Description:
Sets the scaling of the dynamic current controller pre-control for the torque/force-generating current component Isq.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Sets the proportional gain of the current controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Sets the integral-action time of the current controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1715
Description:
Displays the actual output of the Isq current controller (torque/force generating current, PI controller).
The value contains the proportional and integral components of the PI controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
p1702[0...n]
Isd current controller pre-control scaling / Isd_ctr_prectrScal
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6714
Min Max
Factory
setting
0.0 [%]
200.0 [%]
70.0 [%]
p1703[0...n]
Isq current controller pre-control scaling / Isq_ctr_prectrScal
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6714
Min Max
Factory
setting
0.0 [%]
200.0 [%]
60.0 [%]
p1715[0...n]
Current controller P gain / I_ctrl Kp
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6714
Min Max
Factory
setting
0.000 100000.000
0.000
p1717[0...n]
Current controller integral-action time / I_ctrl Tn
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
5714, 6700, 6714,
7017
Min Max
Factory
setting
0.00 [ms]
1000.00 [ms]
2.00 [ms]
r1718
CO: Isq controller output / Isq_ctrl outp
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6714
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......