9 - 4
9. GENERAL GAIN ADJUSTMENT
9.2.2 Auto tuning mode basis
The block diagram of real-time auto tuning is shown below.
0 0 0
M
Command
Automatic setting
Loop gains
PG1,VG1
PG2,VG2,VIC
Current
control
Set 0 or 1 to turn on.
Current feedback
Real-time auto
tuning section
Switch
Load inertia
moment
Encoder
Servo motor
Position/speed
feedback
Speed feedback
Load inertia
moment ratio
estimation section
Gain
table
Parameter No.PB06
Load inertia moment
ratio estimation value
Parameter No.PA08 Parameter No.PA09
Gain adjustment mode
selection
Response
setting
When a servo motor is accelerated/decelerated, the load inertia moment ratio estimation section always
estimates the load inertia moment ratio from the current and speed of the servo motor. The results of
estimation are written to parameter No.PB06 (the ratio of load inertia moment to servo motor). These results
can be confirmed on the status display screen of the MR Configurator section.
If the value of the load inertia moment ratio is already known or if estimation cannot be made properly, set the
"auto tuning mode 2" (parameter No.PA08: 0002) to stop the estimation of the load inertia moment ratio
(Switch in above diagram turns off), and set the load inertia moment ratio (parameter No.PB06) manually.
From the preset load inertia moment ratio (parameter No.PB06) value and response level (parameter
No.PA09), the optimum loop gains are automatically set on the basis of the internal gain table.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 60 minutes since power-on. At
power-on, auto tuning is performed with the value of each loop gain saved in the EEP-ROM being used as an
initial value.
POINT
If sudden disturbance torque is imposed during operation, the estimation of
the inertia moment ratio may malfunction temporarily. In such a case, choose
the "auto tuning mode 2" (parameter No.PA08: 0002) and set the correct load
inertia moment ratio in parameter No.PB06.
When any of the auto tuning mode 1 and auto tuning mode settings is
changed to the manual mode 2 setting, the current loop gains and load inertia
moment ratio estimation value are saved in the EEP-ROM.
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...