3 - 14
3. CC-LINK COMMUNICATION FUNCTIONS
Signal name
Description
Device No.
Remarks
1 station
occupied
2 stations
occupied
Monitor output execution
demand
When RYn8 is turned ON, the following data and signals are set.
At the same time, RXn8 turns ON. While RYn8 is ON, the
monitor values are kept updated.
1) When 1 station is occupied
Remote register RWrn: Data demanded by Monitor 1 (RWwn)
Remote register RWrn 1: Data demanded by Monitor 2
(RWwn+1)
Remote register RWrn 2: Respond code indicating normal or
error
2) When 2 stations are occupied
Remote register RWrn: Lower 16 bits of data demanded by
Monitor 1 (RWwn)
Remote register RWrn 1: Upper 16 bits of data demanded
by Monitor 1 (RWwn)
Remote register RWrn 5: Lower 16 bits of data demanded
by Monitor 2 (RWwn+2)
Remote register RWrn 6: Upper 16 bits of data demanded
by Monitor 2 (RWwn+2)
Remote register RWrn 2: Respond code indicating normal or
error
RYn8 RYn8
Instruction code execution
demand
Turning RYn9 ON executes the processing corresponding to the
instruction code stored in remote register RWwn 2.
After completion of instruction code execution, the respond code
indicating normal or error is set to RWrn 2. At the same time,
RXn9 turns ON.
Refer to section 16.2.4 for details.
RYn9 RYn9
Point table No. selection 1
The point table No. and the home position return are selected by
RYnA to RY(n 2)5.
RYnA RYnA
1
2
Point table No. selection 2
1
2
3
4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(Note 1) RY of CC-Link
Point
table No.
RYnE RYnD RYnC RYnB RYnA
(Note 2)
254
255
Note 1. 0: OFF 1: ON
2. Home position return is a setting
RY
(n+2)5
RY
(n+2)4
RY
(n+2)3
RYnB RYnB
Point table No. selection 3
RYnC
RYnC
Point table No. selection 4
RYnD
RYnD
Point table No. selection 5
RYnE
RYnE
Point table No. selection 6
RY(n 2)3
Point table No. selection 7
RY(n 2)4
Point table No. selection 8
RY(n 2)5
Clear
When the parameter No.PD22 setting is "
1", the position
control counter droop pulses is cleared at the leading edge of
RYnF. The pulse width should be 10ms or more.
When the parameter No.PD22 setting is "
2", the pulses
are always cleared while RYnF is on.
RYnF RYnF
1
2
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...