14. OPTIONS AND AUXILIARY EQUIPMENT
14.10 Molded-case circuit breakers, fuses, magnetic contactors
CAUTION
To prevent the servo amplifier from smoke and a fire, select a molded-case circuit
breaker which shuts off with high speed.
Always use one molded-case circuit breaker and one magnetic contactor with one
servo amplifier.
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in
this section.
Servo amplifier
Molded-case circuit breaker (Note 4)
Fuse
Magnetic
contactor
(Note 2)
Not using power
factor improving
reactor
Using power
factor improving
reactor
Voltage
AC
Class
(Note 1)
Current [A]
Voltage
AC [V]
MR-J3-10T (1)
30A frame 5A
30A frame 5A
240V
10
250
S-N10
S-T10
MR-J3-20T
30A frame 5A
30A frame 5A
10
MR-J3-20T1
30A frame 10A
30A frame 10A
15
MR-J3-40T
30A frame 10A
30A frame 5A
15
MR-J3-
60T 70T 100T 40T1
30A frame 15A
30A frame 10A
20
MR-J3-200TN
30A frame 20A
30A frame 15A
40
S-N20
(Note 3)
S-T21
MR-J3-350T
30A frame 30A
30A frame 30A
70
S-N20
S-T21
MR-J3-500T
50A frame 50A
50A frame 40A
125
S-N35
MR-J3-700T
100A frame 75A 50A frame 50A
150
S-N50
MR-J3-11KT
100A frame 100A 100A frame 75A
T
200
S-N65
MR-J3-15KT
125A frame 125A 100A frame 100A
250
S-N95
MR-J3-22KT
225A frame 175A 225A frame 150A
350
S-N125
MR-J3-60T4
30A frame 5A
30A frame 5A
600Y/347V
10
600
S-N10
S-T10
MR-J3-100T4
30A frame 10A
30A frame 10A
15
MR-J3-200T4
30A frame 15A
30A frame 15A
25
MR-J3-350T4
30A frame 20A
30A frame 20A
35
S-N20
(Note 3)
S-T21
MR-J3-500T4
30A frame 30A
30A frame 30A
50
MR-J3-700T4
50A frame 40A
50A frame 30A
65
S-N20
S-T21
MR-J3-11KT4
60A frame 60A
50A frame 50A
100
S-N25
MR-J3-15KT4
100A frame 75A 60A frame 60A
150
S-N35
MR-J3-22KT4
225A frame 125A 100A frame 100A
175
S-N65
Note 1. When not using the servo amplifier as a UL/cUL Standard compliant product, K5 class fuse can be used.
2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80ms or less.
3. S-N18 can be used when auxiliary contact is not required.
4. Use a molded-case circuit breaker which has the same or more operation characteristics than our lineup.
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...