3 - 41
3. CC-LINK COMMUNICATION FUNCTIONS
3.7 Function-by-function programming examples
This section explains specific programming examples for servo operation, monitor, parameter read and write,
and others on the basis of the equipment makeup shown in section 3.7.1.
3.7.1 System configuration example
As shown below, the CC-Link system master local unit is loaded to run two servo amplifiers (1 station
occupied / 2 stations occupied).
(1) System configuration
Programmable controller
Station No.1
Y30
Station No.2
Power supply
Q62P
CPU
Q02HCPU
Master station
QJ61BT11N
(X/Y00 to 1F)
Input module
QX40
(X20 to X2F)
Output module
QY40P
(Y30 to Y3F)
Terminating
resistor
X20 to
Servo amplifier
(1 station occupied)
Terminating
resistor
Servo amplifier
(2 stations occupied)
(2) Master station network parameter setting
In the programming examples, network parameters are set as below.
Item
Setting condition
Item
Setting condition
Start I/O No.
0000
Remote register (RWr)
W0
Data link disorder
station settings
Clear
Refresh
device
Operational setting
(No check on
"Hold input data")
Remote register (RWw)
Refresh device
W100
Case of CPU
Refresh
Special relay (SB)
SB0
STOP
setting
Refresh
device
Type
Master station
Special relay (SW)
SW0
Mode
Remote net
Refresh device
(Ver.1 mode)
Retry count
3
All connect count
2
Automatic reconnection station count
1
Remote input (RX)
X1000
CPU down select
Stop
Refresh device
Scan mode setting
Asynchronous
Remote output (RY)
Y1000
Refresh device
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...