14 - 93
14. OPTIONS AND AUXILIARY EQUIPMENT
Table 14.4 Servo motor’s leakage current example (Igm)
Table 14.5 Servo amplifier's leakage current example (Iga)
Servo motor output [kW]
Leakage current [mA]
Servo amplifier capacity [kW]
Leakage current [mA]
0.05 to 1
0.1
0.1 to 0.6
0.1
2
0.2
0.75 to 3.5 (Note)
0.15
3.5 0.3
5 7 2
5 0.5
11 15 5.5
7 0.7
22 7
11 1.0
Note. For the 3.5kW of 400V class, leakage current is 2mA,
which is the same as for 5kW and 7kW.
15 1.3
22 2.3
Table 14.6 Earth-leakage circuit breaker selection example
Servo amplifier
Rated sensitivity current of earth-
leakage circuit breaker [mA]
MR-J3-10T to MR-J3-350T
MR-J3-10T1 to MR-J3-40T1
MR-J3-60T4 to MR-J3-350T4
15
MR-J3-500T(4) 30
MR-J3-700T(4) 50
MR-J3-11KT(4) to MR-J3-22KT(4)
100
(2) Selection example
Indicated below is an example of selecting an earth-leakage current breaker under the following conditions.
M
0.4kW
NV
2mm
2
× 5m
2mm
2
× 5m
Servo amplifier
Servo motor
HF-KP43
Igm
Ig2
Iga
Ig1
Use an earth-leakage current breaker generally available.
Find the terms of Equation (14.1) from the diagram.
Ig1 20
1000
5
0.1 [mA]
Ig2 20
1000
5
0.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (14.1).
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4.0 [mA]
According to the result of calculation, use an earth-leakage current breaker having the rated sensitivity
current (Ig) of 4.0[mA] or more. An earth-leakage current breaker having Ig of 15[mA] is used with the NV-
SP/SW/CP/CW/HW series.
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...