3 - 51
3. CC-LINK COMMUNICATION FUNCTIONS
(3) Servo amplifier alarm resetting program examples
(a) Deactivate the alarm of the servo amplifier of station 2 by issuing a command from the programmable
controller.
Reset the servo amplifier on the occurrence of a servo alarm by turning on X20.
Checks data link status of station No.2.
Turns on reset command (RY5A).
Turns off reset command (RY5A) when trouble
flag (RX5A) turns off.
Trouble
flag
Reset
command
(b) Deactivate the alarm of the servo amplifier of station 2 using the instruction code.
Code No.
Description
H8010
Alarm reset command (hexadecimal)
Set data
Description
H1EA5
Execution data (hexadecimal)
Reset the servo amplifier by turning on X20.
The respond code at instruction code execution is set to D2.
Writes alarm reset command (H8010) to
RWw6 and execution data (H1EA5) to RWw7.
Turns on instruction code execution demand
(RY29).
Reads respond code (RWr6) to D2 when
instruction code execution completion (RX29)
turns on.
Reset command
Turns off instruction code execution demand
(RY29).
Checks data link status of station No.2.
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...