6 - 16
6. PARAMETERS
No. Symbol
Name and function
Initial value
Unit
Setting
range
PB02 VRFT Vibration suppression control tuning mode (Advanced vibration suppression
control)
The vibration suppression is valid when the parameter No.PA08 (auto tuning
mode) setting is " 2" or " 3". When PA08 is " 1", vibration
suppression is always invalid.
Select the setting method for vibration suppression control tuning. Setting this
parameter to " 1" (vibration suppression control tuning mode)
automatically changes the vibration suppression control - vibration frequency
(parameter No.PB19) and vibration suppression control - resonance frequency
(parameter No.PB20) after the predetermined number of positioning operations
is executed.
Droop pulse
Command
Automatic
adjustment
Droop pulse
Command
Machine side
position
Machine side
position
Vibration suppression control tuning mode
0 0 0
0000h
Setting
Vibration suppression
control tuning mode
Automatically set
parameter
0
Vibration suppression
control OFF
(Note)
1
Vibration suppression
control tuning mode
(Advanced vibration
suppression control)
Parameter No.PB19
Parameter No.PB20
2
Manual
mode
Note. Parameter No.PB19 and PB20 are fixed to the initial values.
When this parameter is set to " 1", the tuning is completed after the
predetermined number of positioning operations are executed for the
predetermined period of time, and the setting changes to " 2". When the
vibration suppression control tuning is not necessary, the setting changes to "
0". When this parameter is set to " 0", the initial values are set to the
vibration suppression control - vibration frequency and vibration suppression
control - resonance frequency. However, this does not occur when the servo off.
PB03
For manufacturer setting
Do not change this value by any means.
0000h
PB04
FFC
Feed forward gain
Set the feed forward gain. When the setting is 100%, the droop pulses during
operation at constant speed are nearly zero. However, sudden
acceleration/deceleration will increase the overshoot. As a guideline, when the
feed forward gain setting is 100%, set 1s or more as the acceleration time
constant up to the rated speed.
0 % 0
to
100
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...