16 - 10
16. INDEXER POSITIONING OPERATION
(2) Output signals (Output device)
POINT
The output devices can be used for both the RX of CC-Link and the external
output signals of CN6 connector.
The signal whose Device No. field has an oblique line cannot be used in CC-Link.
Signal name
(Device name)
Description
Device No.
1 station
occupied
2 stations
occupied
Ready
A ready is assigned to the CN6-14 pin as an external output signal. RXn0
turns ON when the servo amplifier is ready to operate after servo-on.
RXn0 RXn0
In position
RXn1 turns ON when the droop pulse value is within the preset in-position
range.
The in-position range can be changed using parameter No.PA10.
Increasing the in-position range may result in a continuous conduction
status during low-speed rotation.
RXn1 turns ON at servo-on.
RXn1 RXn1
Rough match
RXn2 turns ON when the command remaining distance becomes less than
the rough match output range set in the parameter. This is not outputted
during base circuit shut-off.
RXn2 turns ON at servo-on.
RXn2 RXn2
Home position return
completion
The home position return completion is assigned to the CN6-16 pin as an
external output signal. RXn3 turns ON when a home position return is
completed. RXn3 turns ON at completion of a home position return.
In an absolute position detection system, RXn3 turns ON when operation is
ready to start, but turns OFF in any of the following cases.
1) Servo-on (RYn0) is turned OFF.
2) Forced stop (EMG) is turned OFF.
3) Reset (RY(n 1)A or RY(n 3)A) is turned ON.
4) Alarm occurs.
5) Forward rotation stroke end (RYn4) or Reverse rotation stroke end
(RYn5) is turned OFF.
6) Home position return has not been made after product purchase.
7) Home position return has not been made after occurrence of Absolute
position erase (A25) or Absolute position counter warning (AE3).
8) Home position return has not been made after electronic gear change.
9) Home position return has not been made after the absolute position
detection system was changed from invalid to valid.
10) Parameter No.PA14 (Station No. direction selection) has been
changed.
11) While a home position return is being made.
When any of 1) to 11) has not occurred and a home position return is
already completed at least once, Home position return completion (RXn3)
turns to the same output status as Ready (RXn0).
RXn3 RXn3
Limiting torque
RXn4 turns ON when the torque is reached at the time of torque
generation.
RXn4 RXn4
Electromagnetic brake
interlock
RXn6 turns OFF at servo-off or alarm occurrence. At alarm occurrence, it
turns OFF independently of the base circuit status.
RXn6 RXn6
Monitoring
Refer to Monitor output execution demand (RYn8).
RXn8
RXn8
Instruction code execution
completion
Refer to Instruction code execution demand (RYn9).
RXn9
RXn9
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...