4 - 18
4. SIGNALS AND WIRING
(b) Termination of the cables
Solid wire: After the insulator has been stripped, the cable can be used as it is.
Insulator
8mm to 9mm
Core
Twisted wire: Use the cable after stripping the insulator and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the
core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the wires
together.
Cable size
Bar terminal type
Crimping tool (Note 2)
[mm
2
]
AWG
For 1 cable
For 2 cable
1.25/1.5 16
AI1.5-10BK
(Note 1)
AI-TWIN2
1.5-10BK
(Note 1)
Variocrimp 4 206-204
2 14 216-205
(Note
2)
Note 1. Manufacturer: Phoenix Contact
2. Manufacturer: WAGO
c) The twin type connector for CNP2 (L
11
L
21
): 721-2105/026-000 (WAGO)
Using this connector enables passing a wire of control circuit power supply.
Refer to appendix 2 for details of connector.
L
21
L
11
L
21
L
11
Power supply
or Front axis
Rear axis
CNP2
Twin type connector for CNP2
(3) MR-J3-350T
(a) Servo amplifier power supply connectors
Servo amplifier power supply connectors
Applicable cable example
Cable finish OD: to 5mm
Applicable cable example
Cable finish OD: to 3.8mm
Connector for CNP1
PC4/6-STF-7.62-CRWH
(Phoenix Contact)
Connector for CNP3
PC4/3-STF-7.62-CRWH
(Phoenix Contact)
Connector for CNP2
54928-0520 (Molex)
CNP1
CNP3
CNP2
Servo amplifier
Summary of Contents for Melservo-J3 Series MR-J3-B
Page 19: ...10 MEMO ...
Page 55: ...1 36 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 61: ...2 6 2 INSTALLATION MEMO ...
Page 179: ...4 58 4 SIGNALS AND WIRING MEMO ...
Page 241: ...5 62 5 OPERATION MEMO ...
Page 357: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 385: ...11 28 11 TROUBLESHOOTING MEMO ...
Page 397: ...12 12 12 OUTLINE DRAWINGS MEMO ...
Page 755: ...17 70 17 SPEED CONTROL OPERATION MEMO ...
Page 793: ...App 38 APPENDIX MEMO ...
Page 799: ...MEMO ...