42
Wiring
Section 3-4
3-4-3
Connecting Origin and Positioning Completed Input Signals
The examples below show input connections when open collector sensor out-
put and the encoder’s Z-phase line driver output are used.
Use a sensor with no chattering, such as a photoelectric sensor, for the origin
input signal.
!Caution
Connect a switch with a switching capacity of at least 5 mA to the 24-V origin
input signal terminal.
!Caution
Do not connect the 5-VDC origin input signal input to any output circuit except
the line driver.
!Caution
Use either the 24-V origin input signal or the 5-V origin input signal, but not
both. Also, be sure not to connect them to the wrong terminal. Using both sig-
nals or connecting them to the wrong terminal will result in damage to internal
circuitry.
24-VDC
power
supply
External
interrupt
input signal
Emergency
stop input
signal
Origin
proximity
input signal
CW limit
input signal
CCW limit
input signal
680
Ω
4.7 k
Ω
(1/2W)
680
Ω
680
Ω
680
Ω
680
Ω
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
Switch (N.O. contact)
Switch (N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
Position Control Unit
Summary of Contents for CS1W-213 - REV 02-2008
Page 2: ...CS1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 43: ...18 Basic Operational Flow Section 2 1 ...
Page 87: ...62 Servo Relay Unit Section 3 7 ...
Page 199: ...174 Z phase Margin Section 6 8 ...
Page 217: ...192 Sample Program Section 7 7 ...
Page 285: ...260 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 377: ...352 Common Parameter Area Appendix C ...