![Omron CS1W-213 - REV 02-2008 Operation Manual Download Page 158](http://html1.mh-extra.com/html/omron/cs1w-213-rev-02-2008/cs1w-213-rev-02-2008_operation-manual_742355158.webp)
133
Writing Data with IOWR
Section 5-4
Method
Outline
Characteristics
Method 1 The transferred
data is immedi-
ately written to
the data area.
The data specified with the IOWR instruction is written to the data area within one cycle.
The number of items (words) that can be transferred with one IOWR instruction is limited as
follows:
When changing position data and executing memory operation, it is possible to transfer the
data to the PCU and send the instruction to start operation within one cycle.
Method 2 The data is writ-
ten to the data
area only after it
has all been
received in a
receive buffer.
Up to 128 words of data can be transferred in one operation. If the number of words to be
transferred is greater than the limits for method 1 listed above, method 2 will be used auto-
matically.
With this method, because data is written to the data area only after it has all been received
in the receive buffer, if the IOWR instruction is used more than once in the ladder program,
it may take 2 or more cycles for transfer to be completed. (See the following example.) This
is different from method 1, where data transfer is completed within one cycle.
If the IOWR instruction is used only once in the ladder program, it is possible to transfer the
data to the PCU and send the instruction to start operation within one cycle, in the same
way as method 1.
Data name
Number/Size
Parameter
I/O setting
1 (1 word)
Operation mode selection
1 (1 word)
Maximum speed
1 (2 words)
Initial speed
1 (2 words)
Origin search high speed/proximity speed
2 (4 words)
Origin compensation
1 (2 words)
Backlash compensation
1 (1 word)
Backlash compensation speed
1 (2 words)
Acceleration/deceleration curve
1 (1 word)
Origin search acceleration time
1 (2 words)
Origin search deceleration time
1 (2 words)
Positioning monitor time
1 (1 word)
CCW software limit
1 (2 words)
CW software limit
1 (2 words)
Pulse rate numerator
1 (1 word)
Pulse rate denominator
1 (1 word)
Initial one pulse speed
1 (1 word)
Data
Sequence data
1 (3 words)
Speed data
6 (12 words)
Position data
6 (12 words)
Acceleration times
12 (12 words)
Deceleration times
12 (12 words)
Dwell times
12 (12 words)
Zones
3 (12 words)
Summary of Contents for CS1W-213 - REV 02-2008
Page 2: ...CS1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 43: ...18 Basic Operational Flow Section 2 1 ...
Page 87: ...62 Servo Relay Unit Section 3 7 ...
Page 199: ...174 Z phase Margin Section 6 8 ...
Page 217: ...192 Sample Program Section 7 7 ...
Page 285: ...260 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 377: ...352 Common Parameter Area Appendix C ...