294
Override
Section 10-6
10-6 Override
10-6-1 Changing Speed During Pulse Output
Overview
• Override can be used to change the speed during pulse output.
• The target speed is determined by the override coefficient set in the oper-
ating data area.
• In order to use the actual target speed that has been set, either disable
the override or set it to 100%.
Operation Example
The following is an example of changing the speed with override during con-
tinuous operation.
1,2,3...
1.
When the operation start switch is turned ON, pulse output is executed at
a speed of 300 pps CW on the X axis.
2.
When speed change switch 1 is turned ON, the pulse output decelerates
to a speed of 150 pps.
3.
When speed change switch 2 is turned ON, the pulse output accelerates
to a speed of 500 pps.
4.
When speed change switch 3 is turned ON, the pulse output decelerates
to a speed of 300 pps.
5.
When the operation start switch is turned OFF, the output of X axis stops.
Setting the PCU
Unit number:
Unit #0
PCU used:
NC113
Operation
starts
Speed (pps)
Time
Speed
change 1
Speed
change 2
Speed
change 3
Operation
stops
150
Summary of Contents for CS1W-213 - REV 02-2008
Page 2: ...CS1W NC113 213 413 133 233 433 Position Control Units Operation Manual Revised February 2008 ...
Page 3: ...iv ...
Page 13: ...xiv ...
Page 15: ...xvi ...
Page 19: ...xx ...
Page 43: ...18 Basic Operational Flow Section 2 1 ...
Page 87: ...62 Servo Relay Unit Section 3 7 ...
Page 199: ...174 Z phase Margin Section 6 8 ...
Page 217: ...192 Sample Program Section 7 7 ...
Page 285: ...260 Easy Backup Function Ver 2 0 or later Section 9 11 ...
Page 377: ...352 Common Parameter Area Appendix C ...